Call Us Today !  +92-21 32361313-18  |   info@chemcoiwt.com

Boiler Water Treatment

Chemco proposes a comprehensive boiler water treatment solutions in Pakistan, based on specific problems known to the boiler system running on high purity feedwater. Chemco’s boiler water treatment solution is geared towards improving efficiency by addressing the problem of high purity feed water while at the same recognizing future pitfalls that may be incurred thus increasing the longevity of the entire system.

Oxygen Corrosion

Even with the presence of a high-efficiency deaeration system dissolved oxygen sometimes does slip through and enter boiler drums. Mechanical deaeration also at times does face operational problems leading to excessive leakage of dissolved oxygen into the boiler water treatment system.

Oxygen corrosion will take place even with an oxygen level of as low as 10 ppb and the results of the corrosion will be significant pitting at the waterline and to a certain extent pitting on tube surfaces.

The use of boiler water treatment chemicals like hydrazine as a chemical oxygen scavenger has been known to provide an excellent result at a very good cost factor but the classification of the product as a suspect carcinogen has made it replaced in many established organizations.

Chemco is proposing Catalyzed Sodium Sulfite based oxygen scavenger. It is a volatile metal passivator and more reactive than any other product, even at lower temperatures.

Boiler Water Treatment Services Provided by Chemco

  1. Plant and system audit and survey
  2. Analysis of water and interpretation of results
  3. Full chemical treatment  program and  recommendation  together with a comprehensive monitoring regime
  4. Periodic (daily, weekly or monthly) field technical services which will include water analysis,  plant performance  monitoring,
    chemical  re-evaluation, trouble-shooting, and comprehensive technical report and recommendations
  5. Inspection of equipment such as  condenser,  heat  exchanger, and  boiler during plant or equipment shutdown
  6. Laboratory analysis of deposit and interpretation of results
  7. Technical on-site and classroom training regarding water treatment and water-related problem
  8. Laboratory and site evaluation on microbiological related problems
  9. Chemical dosing system and monitoring automation
  10. Statistical process control and parameters monitoring computer software.

Boiler Products

Caustic Corrosion

For internal treatment to prevent the phenomena of caustic corrosion trisodium phosphate will be blended with disodium phosphate. This is to achieve a congruent point. Potential deposition of corrosion products will be eliminated by the presence of condensate polisher.

Condensate Corrosion

Condensate corrosion is a  result of the formation of carbonic acid as leak carbon dioxide that flashes off together with condensing with steam. It has been identified as one of the most common forms of corrosion in any steam generation system.

Based on the steam distribution structure Chemco is proposing a  blend of morpholine and cyclohexylamine for complete neutralization of the return condensate to prove comprehensive protection on the system piping and equipment.